Solid State Combustible and CO Gas Sensor Module 4100-XX

Sierra Monitor’s 4100-XX module is a simple gas sensor module with a 4-20 mA output signal to detect various combustible gases and Carbon Monoxide (CO).

The 4100-XX module is based on solid state (semiconductor) technology, a simple and robust method of detection capable of detecting low points-per-million (ppm) levels of gases.

Utilizing the solid state MOS (metal oxide semiconductor) technology, the 4100-XX module has a long life cycle and fast response times. The 4100-XX module provides a non-linear 4-20 mA output signal that can interface with the Sentry Controller or other linearizing controllers/indicators. Curves and linearizing equations can be provided for a specific gas and sensor to enable the operation of these sensor modules with other brand controllers. Also, these modules can be calibrated with the gas of interest or with methane or Carbon Monoxide. Thus, the user does not have to obtain a special calibration gas.

Solid State Combustible and CO Gas Sensor Module 4100-XX

  • Non-Linear 4-20 mA DC Output – Industry standard analog output
  • Simple Zero and Span Adjustments – Easily access potentiometers to enable calibration adjustments and reduce maintenance costs

Specifications for Solid State Combustible and CO Gas Sensor Module 4100-XX

Sensor

  • Type: Solid State MOS (Metal Oxide Semiconductor)
  • Range: 20-500 ppm or 50-5000 ppm (See Table A)
  • Response: 80% of concentration in less than 3 min.
  • Typical Life: 1-3 years in Normal Service

Detectable Gases and Vapors

  • Typical List: See Table A

Maintenance

  • Calibration Adjustments: Zero Adjust, Span Adjust
  • Sensor LED: OFF indicates heater or film is an open circuit

Environmental

  • Temperature
    • Operating: 14o to 104oF (-10o to 40 oC)
    • Storage: -67o to 185oF (-55o to 85 oC)
  • Humidity: 5%-95% non-condensing

Electrical Data

  • Wiring: 3 Wire non-isolated
  • Input Voltage: 14 - 30 VDC
  • Current:
    • 70 mA @ 4 mA DC loop current
    • 90 mA @ 20 mA DC loop current at 24 VDC
  • Power: 2.1 watts
  • Output Range: 4-20 mA DC non-linear
  • Loop Resistance: 800 ohms at 28 VDC

Mechanical

  • Size: 6.75 x 4.0 x3.5 inches (17.1 x 10.2 x 8.9 cm)
  • Material: Cast aluminum epoxy painted
  • Weight: 2 lb. (0.9 Kg)
  • Classification: Class I Div. I Groups C, D
  • Mounting: Connects to a vertical ¾” electrical conduit
Table: Gases and ranges for 4100-XX Gas Sensor Modules
GAS 500 PPM FULL SCALE 5,000 PPM FULL SCALE GAS 500 PPM FULL SCALE 5,000 PPM FULL SCALE
acetic acid 4100-34 4100-35 hexafluoropropylene 4100-34 4100-33
acetone 4100-34 4100-35 hydrogen 4100-34
acetonitrile 4100-34 4100-35 methane 4100-35
acetylene 4100-34 4100-35 methanol 4100-34 4100-35
acrylonitrile 4100-34 4100-35 methyl bromide 4100-34 4100-35
ammonia (<0°C) 4100-34 methyl chloride 4100-34 4100-35
ammonia (>0°C) 4100-36 methyl ethyl ketone 4100-34 4100-35
benzene 4100-34 methyl propyl ketone 4100-34 4100-35
1-butanol 4100-34 methylene chloride 4100-34
2-butanol 4100-34 nitroethane 4100-34 4100-35
i-butane 4100-34 4100-35 nitromethane 4100-34 4100-35
n-butane 4100-34 4100-35 1-pentanol 4100-34 4100-35
1-butanol 4100-35 propanal 4100-35
2-butanol 4100-35 propane 4100-34
i-butanol 4100-34 4100-35 i-propanol 4100-34 4100-35
t-butanol 4100-34 4100-35 n-propanol 4100-34 4100-35
butene 4100-34 4100-35 propylene 4100-34 4100-35
carbon monoxide 4100-34 R-11 4100-33
chloroform 4100-34 R-12 4100-33
cyclohexane 4100-34 4100-35 R-22 4100-33
cyclopentane 4100-34 4100-35 R-113 4100-33
diethylketone 4100-34 4100-35 R-123 4100-33
dipropylether 4100-34 4100-35 R-134a 4100-33
ethane 4100-34 4100-35 R-141-b 4100-33
ethanol 4100-34 4100-35 R-142b 4100-33
ethylene 4100-34 4100-35 R-500 4100-33
n-heptane 4100-34 4100-35 R-502 4100-33
n-hexane 4100-34 4100-35 toulene 4100-34
1-hexanol 4100-34 4100-35 xylene 4100-34

How to Purchase Solid State Combustible and CO Gas Sensor Module

Find Your Local Sales Partner

We work with a variety of sales partners around the world to increase our ability to reach customers. If you are looking to purchase the Solid State Combustible and CO Gas Sensor Module (4100-XX), please contact the sales partner that covers your location:

Contact Us