Multi IR Flame Detector 3600-M

Sierra Monitor’s 3600-M flame detector monitors hydrocarbon and hydrogen flames at long distances with the highest immunity to false alarms.

The 3600-M uses infrared (IR) technology, a reliable design that provides early warning of flaming fires and immunity to false alarms from IR sources such as sunlight and IR projectors.

The 3600-M utilizes a Multi-Spectrum Design, allowing it to detect hydrocarbon and hydrogen flames up to 215 feet away. It can detect a gasoline pan fire at 215 feet or a hydrogen flame at 100 feet in less than 5 seconds. Users can also select different sensitivity levels to ensure no other detectors cross-over detection zones. Other features include a heated window to eliminate condensation and icing, HART and Modbus capabilities for digital communications, low power requirements, and a compact design.

The Multi IR Flame Detector 3600-M is approved and certified by a variety of third party agencies, including FM, ATEX, IECEx, TUV, and CSA. These approvals and certifications assure our customers that we carry only the highest quality of products and performance.

Multi IR Flame Detector 3600-M

  • Multi-Spectrum Design – Detect hydrocarbon and hydrogen flames up to 215 feet away
  • IR Sensitivity Selection – Choose between short and long distance sensitivity ranges, depending on the needs and function
  • 5-Second Response – Quickly respond and alarm users of a fire in a swift manner
  • Heated Window – Eliminate any possible condensation or icing to ensure the detector to function properly
  • Low Power Requirements – Save energy costs while protecting the facility
  • Multiple Output Options (Relay Outputs, 0-20 mA, HART, MODBUS RS-485) - Easily install in a variety of field applications and easily obtain critical safety information wherever needed with maximum flexibility and compatibility

Specifications for Multi IR Flame Detector 3600-M

Model Number

  • 3600-M

Spectral Response

  • Multi IR Bands

Detection Range

(At highest Sensitivity Setting for 1 sq. ft. / 0.1 sq. m pan fire)


215 ft. (65 m)n-Heptane
215 ft. (65 m)Gasoline
150 ft. (45 m)Diesel Fuel
150 ft. (45 m)JP5
100 ft. (30 m)Hydrogen*
150 ft. (45 m)Kerosene
135 ft. (40 m)Ethanol 95%
115 ft. (35 m)Methanol
135 ft. (40 m)
IPA (Isopropyl Alcohol)
100 ft. (30 m)Methane*
100 ft. (30 m)LPG*
16 ft. (5 m)Polypropylene Pellets
33 ft. (10 m)Office Paper

*20” (0.5 m) high, 8” (0.2 m) with plume fire

Response Time

  • Typically 5 seconds

Adjustable Time Delay

  • Up to 30 seconds

Sensitive Range

  • 4 Sensitive Ranges for 1 sq. ft. (0.1 sq. m) n-heptane pan fire from 50 ft. (15 m) to 215 ft. (65 m)

Field of View

  • Gasoline: 67o horizontal, 70o vertical
  • Hydrogen: 80o horizontal, 80o vertical

Built-in-Test (BIT)

  • Manual and Automatic

Temperature Range

  • Operating: -67oF to 167oF (-55oC to 75oC)
  • Operating Option: -67oF to 185oF (-55oC to 85oC)
  • Storage: -67oF to 187oF (-55oC to 85oC)

Humidity

  • Up to 95% non-condensing (withstands up to 100% RH for short periods)

Heated Options

  • To eliminate condensation and icing on the window

Electrical Specifications

  • Operating Voltage: 24 VDC nominal (18-32 VDC)
  • Power Consumption:
    • Standby: Max. 90 mA (110 mA with heated window)
    • Alarm: Max. 130 mA (160 mA with heated window)
  • Cable Entries: 2 x ¾” - 14 NPT conduits or 2 x M25 x 1.5 mm ISO
  • Wiring: 12 - 22 AWG (2.5 mm 2 - 0.3mm2)
  • Electrical Input Protection: According to MIL-STD-1275B
  • Electromagnetic Compatibility: EMI/RFI protected to EN61326-3 and EN61000-6-3
  • Electrical Interface: The detector includes twelve (12) terminals with five (5) wiring options (factory set)

Outputs

  • Relays:
    • Alarm, Fault, and Auxiliary
    • SPST volt-free contacts rated 5A at 30 VDC or 250 VAC
  • 4-20 mA (stepped)
    • Sink (source option) configuration
      • Fault: 0 + 1 mA
      • Warning: 16 mA +/- 5%
      • BIT Fault: 2 mA +/- 10%
      • Alarm: 20 mA +/- 5%
      • Normal: 4 mA +/- 10%§  Resistance Loop: 100-600 ohms
  • HART Protocol: Optional HART communication on the 0-20 mA analog current (FSK) – used for maintenance, configuration changes and asset management, available in mA source output wiring options
  • RS-485: RS-485 Modbus compatible communication link that can be used in computer control installations

Mechanical Specifications

  • Materials: Stainless Steel 316L with electro polish finish (FM or ATEX Approval)
  • Mounting: Stainless Steel 316L with electro polish finish
  • Dimensions:
    • Detector: 4” x 4.6” x 6.18” (101.6 x 117 x 157 mm)
  • Weight
    • Aluminum: 2.8 lb. (1.3 Kg)
    • Stainless Steel 316L: 6.1 lb. (2.8 Kg)
    • Tilt Mount: 2.2 lb. (1.0 Kg)
  • Environmental Standards: Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
  • Water and Dust: IP66 and IP67 per En60529, NEMA 250 6P

Approvals

  • Hazardous Area
    •  ATEX & IECEx
      • Ex II 2 GD
      • Ex de IIB + H2 T5 (-55o to 75 oC)
      • Ex de IIB + H2 T4 (-55o to 85 oC)
      • Ex tD A21 IP66/X7 T 95oC
      • Ex tD A21 IP66/X7 T 105oC
    • FM/CSA
      • Class I Div. 1, Groups, B, C & D
      • Class II/III Div. 1, Groups E, F & G
  • Performance
    • EN54-10 (LPCB)
    • FM-3260 (FM)
  • Reliability
    • IEC61508 – SIL-2 (TUV)
    • PDO Approval: Petroleum Development Oman Certificate of Registration
    • ISO 9001:2008: Registered Quality System

Accessories

  • Fire Simulator: 20/20-310
  • Tilt Mount: 3600-01
  • Weather Protector: 777163
  • Air Shield: 777650
  • Mini Laptop Kit: 777820
  • USB RS-485 Harness Kit: 794079-5
  • Laser Pointer (Detector Area Coverage): 777166